ENMG / CABINET HEATING
CSP028
Compact PTC cabinet fan heaters
DIN-rail PTC fan heaters for warming enclosed control cabinets and reducing condensation risk.
Request a quote ↗TECHNICAL DATA / CSP028
Specifications & selection.
- 150, 250 and 400 W selection.
- Ball-bearing axial fan and temperature-limiting protection.
- Black PA66 housing; vertical mounting with upward outlet.
| Model | Power | W × H × L | Approximate mass |
|---|---|---|---|
| CSP028-F2150 | 150 W | 75 × 65 × 90 mm | 0.30 kg |
| CSP028-F2250 | 250 W | 85 × 90 × 110 mm | 0.52 kg |
| CSP028-F2400 | 400 W | 85 × 90 × 110 mm | 0.52 kg |
| Parameter | Published specification |
|---|---|
| Supply options | 110–120 VAC or 220–240 VAC, 50/60 Hz; select the correct version |
| Power tolerance | ±20% at 25 °C, vertical with terminals down, indoor convection conditions |
| Heating element | Ceramic semiconductor PTC |
| Fan airflow | 32 / 35 CFM (54 / 60 m³/h); source does not map figures to models or frequency |
| Temperature protection | Fan-failure / overtemperature protection with automatic reset |
| Wiring | Solid conductor maximum 2.5 mm²; flexible maximum 1.5 mm² with ferrule |
| Maximum terminal torque | 0.8 N·m |
| Housing | PA66, black; source specifies UL94 V-0 material |
| Mounting | 35 mm DIN rail, vertical, outlet upward |
| Environment | −45 to +70 °C; ≤90% RH; no condensation or icing |
| Protection | IP20; source labels Class II—confirm earthing instructions |
| Life statement | Text says over 50,000 hours at 25 °C; image contains a conflicting multiplier |
Selection & installation notes
- The naming guide maps voltage code 1 to 110–120 VAC and 2 to 220–240 VAC, but the table puts both ranges against F2 models. Do not treat one unit as automatically dual-voltage; confirm the order code and nameplate.
- The source both requests earthing and calls the unit Class II. Follow the confirmed manufacturer instructions for the exact unit.
- Use ON/OFF control; the source excludes voltage control and PWM. Keep airflow unobstructed and allow clearance around the hot outlet.
- Repeated thermal trips require inspection of fan and airflow. The published life figure is not a warranty or independently verified test result.