ENMG / TEMPERATURE & HUMIDITY TRANSMITTERS

EHTB100-RM

RS485 temperature and humidity transmitter

A compact environmental transmitter for control cabinets and sheltered monitoring locations, with digital temperature and humidity output over Modbus RTU.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / EHTB100-RM

Specifications & selection.

Measurement and operating conditions
ParameterSpecification
Temperature measurement range−40 to +120 °C in technical specification
Humidity measurement range0–100% RH
Typical accuracy at 25 °CTemperature ±0.2 °C; humidity ±1.8% RH
Resolution0.1 °C / 0.1% RH
Device operating / storage temperature−20 to +60 °C / −30 to +70 °C
Operating humidity≤95% RH, non-condensing
Supply / power5–36 VDC / <1 W typical; reverse-polarity protection stated
Ingress / installationIP20 / supplied 3M adhesive pad
Size / mass60 × 30 × 18 mm / 54 g
Modbus RTU register map — source protocol V1.1
AddressPurposeType / scalingAccess
0x0000Station addressuint16; 1–247, default 10x03 read / 0x06 write
0x0001Baud code0=9600, 1=4800, 2=2400; default 00x03 / 0x06
0x0002Temperature offsetint16 / 10 °C; ±10.0 °C, default 00x03 / 0x06
0x0003Humidity offsetint16 / 10% RH; ±10.0% RH, default 00x03 / 0x06
0x0004Temperatureint16 / 10 °C0x04 read
0x0005Humidityuint16 / 10% RH; limited to 0–100% RH0x04 read
Wiring and communication
ParameterValue
Brown / blueVCC+ / GND
White / blackRS485 A / B
Serial format8 data bits, no parity, 1 stop bit
Default / selectable baud9600 / 9600, 4800, 2400 bps
Read temperature and humidity, station 101 04 00 04 00 02 30 0A; includes CRC
Protocol behaviorSlave responds to master requests; no unsolicited reporting; 0x10 not supported

Selection & installation notes

  • The measurement range does not expand the complete-device operating range. Observe −20 to +60 °C and non-condensing conditions for installation.
  • The protocol table permits temperature values up to +125 °C, while the technical measurement specification ends at +120 °C. Confirm the sensor revision before using the extended range.
  • Decode negative temperature and calibration as signed 16-bit integers. The example frame includes CRC; do not append a second CRC. Recalculate CRC after changing any bytes.
  • Assign unique addresses before connecting multiple units. After a baud change, verify with a read at the target rate before repeating a write; a missing reply does not prove the write failed.
  • Use an appropriate RS485 bus, termination and EMC grounding scheme; keep signal wiring away from power cables. IP20 requires a protected, dry installation. The official page currently provides no usable product photograph.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG cabinet environment systems — English product-family brochure.

This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.