ETC5 Universal-input PID temperature controllers

ENMG / TEMPERATURE CONTROLLERS

ETC5

Universal-input PID temperature controllers

Panel and DIN-rail controllers with configurable sensor inputs, autotuning PID, separate process/setpoint displays and optional serial communication.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / ETC5

Specifications & selection.

Panel selection
CodePanel mmCutout mm
N48 × 24Request drawing
S48 × 4845 × 45
W96 × 4892 × 45 in prose; verify drawing
H48 × 96Prose:45 × 92; image:45 × 93 — confirm
M72 × 7269 × 69
L96 × 9693 × 93
D22.5 mm wide DIN versionDIN mounting
Ordering options
FieldOptions
FormatETC5[size]-[output][alarm][supply][terminal]M[communication]
OutputRX: relay; QX: SSR drive; CX: current; QR: SSR drive + relay; RR: two relays
Alarms1 or 2 auxiliary contacts
SupplyA:85–240 VAC 50/60 Hz; D:24 VAC/DC
TerminalsS:screw; P:push-in spring
CommunicationR:RS485 Modbus RTU; blank:none
ExampleETC5S-RX1ASM:48-square, relay, one alarm, AC supply, screw, universal input
Measurement and outputs
ParameterSpecification
ThermocouplesK / J / R / S / B / E / N / T
RTD inputsPt100 / Cu50; verify actual sensor and calibrated range
Analog inputs0–5 V / 1–5 V / 0–20 mA / 4–20 mA
Current-input shuntExternal 250 Ω resistor specified
Measurement / resolution / sample±0.5% FS / 14 bit / 0.5 s
Cold junction compensation±2 °C over 0–50 °C, software correction
Control relaySPDT, 5 A at 250 VAC / 30 VDC, source rating
Alarm relaySPST-NO, 5 A at 250 VAC / 30 VDC, source rating
CX current output4–20 mA / 0–20 mA configurable
Power / ambient<10 VA / 0–50 °C, 30–85% RH, non-condensing
Withstand / insulation1500 VAC, 1 minute / >50 MΩ at 500 VDC
ETC5S depth drawing75 mm; 44 mm body section; allow terminals and clamps
Source temperature-range examples
Sensor / codeRange
K / K070–1372 °C
J / J060–1200 °C
R / R02 and S / S020–1769 °C
B / B01400–1800 °C
E / E020–800 °C
N / N020–1300 °C
T / T01−199.9–400.0 °C
Pt100 / D01−199.9–649.0 °C

Selection & installation notes

  • The instrument range is not the permissible temperature range of the sensor or process. The source’s unusually broad Cu50 ranges require model-specific verification.
  • Source accuracy is not guaranteed for R/S at 0–399 °C or T at −199.9–100 °C. Specify the full-scale range when assessing ±0.5% FS accuracy.
  • An SSR-drive output is a control signal, not a heater power output. Confirm drive voltage/current and external SSR compatibility.
  • Use matching thermocouple compensation wire or three equal RTD leads. Separate sensor wiring from load cables.
  • Provide independent overtemperature protection where required by the heating system. Confirm exact terminal assignments, output ratings and firmware protocol before commissioning.
  • Panel thickness must be below 7 mm; source clearances are >25 mm horizontally and >30 mm vertically. Allow the stated 5–6 s startup preparation time.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.