HAD-350A Integrated cabinet dehumidifier and heater

ENMG / ENCLOSURE DEHUMIDIFIERS

HAD-350A

Integrated cabinet dehumidifier and heater

An integrated Peltier condensation dehumidifier with power supply, humidity/temperature control, PTC heating and RS485 monitoring for electrical enclosures.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / HAD-350A

Specifications & selection.

Performance and electrical data
ParameterSpecification
Supply100–240 VAC,50/60 Hz
Dehumidification input350 W maximum
PTC heater300 W at220 V;230 W at110 V
Standby1.5 W in prose
Water removal1000 mL/24 h at35 °C,85% RH; approximately840 mL/day at35 °C,75% RH
Enclosure size5 m³ recommendation, dependent on moisture ingress and conditions
Humidity measurement0–99% RH;±2% RH
Temperature measurement−40 to +120 °C;±1 °C
Operating ambient−20 to +60 °C
Altitude / pressure≤3000 m /80–110 kPa; verify derating at altitude
Protection / massIP20 /approximately4.1 kg
Original drawing and installation
ParameterValue
Main vertical body length299 mm, excluding drain extension
Overall bracket width / depth149.3 mm /173.1 mm
Body width105 mm
Mounting centers132 mm horizontally;156 mm vertically for illustrated center slots
FasteningM4; verify chosen slot pattern in delivered drawing
Air clearanceAt least80 mm from adjacent equipment
Drain fittingSUS304 barbed,Ø7 mm maximum outside;Ø5 mm bore
Hose in current prose2 m;ID6±0.2 mm,OD9±0.2 mm
OrientationVertical, drain downward; continuously falling hose to outside cabinet
Local settings
MenuFunctionDefault
E1 /E2Humidity start /stop;E1>E275 /65% RH
E3Humidity offset,−10 to+10% RH0
E4 /E5Heating start /stop;E5>E45 /15 °C
E6Temperature offset,−10 to+10 °C0
E7Fan stop delay,1–60 min5 min
E8Device address,1–1281
E9Baud rate9600/4800/24009600
8-position terminal order in original illustration
PositionConnection
1 /2 /3External humidity/temperature sensor:brown /black /blue
4 /5RS485 A(D+) /B(D−)
6Protective earth PE
7 /8AC line L /neutral N
Modbus V1.0 readout reference — zero-based hexadecimal addresses
AddressValueConversion
0x0000Power state0=off,1=on
0x0001Ambient humidityraw/10, %RH
0x0002Ambient temperatureraw/10−50, °C
0x0003TEC temperaturesigned16-bit raw/10, °C
0x0004Output/mode stateBits0/1:dehumidify/heat outputs;bits4/5:modes; confirm write semantics
0x0005Fault bitsBit0:sensor;1:NTC;2:TEC;3:fan

Selection & installation notes

  • The source prose incorrectly calls156 mm the horizontal mounting spacing. The original drawing shows it vertically, with132 mm horizontal centers. Confirm the supplied drawing before drilling.
  • The wiring illustration says110–220 VAC, while the technical table and prose say100–240 VAC. Verify the delivered nameplate. Heater power is separate from the350 W dehumidification figure; confirm simultaneous total input and fuse sizing.
  • Hose and display specifications differ by source: the older image saysD8 mm hose and resolution1.0; current prose specifies6/9 mm hose and0.1 °C/1% RH display. Match the actual supplied fitting and firmware.
  • Removal capacity falls as air becomes cooler or drier. The5 m³ recommendation is not a guarantee for leaky enclosures or very low humidity; the source discourages operation below15 °C with target humidity below35% RH.
  • Keep condensate outside the enclosure, prevent backflow and avoid open trays inside the cabinet. Connect PE and separate mains, sensor and RS485 wiring.
  • Protocol uses8N1 and CRC low byte first. Reads use0x03; writes require the firmware-specific map. Source0x10 is restricted to exactly seven registers0x0006–0x000C; the device may silently ignore invalid requests.
  • Settings-temperature registers use a different offset from ambient-temperature readings. Do not copy a readout conversion into a write command.
  • Double-clicking Return restores factory settings; record commissioned parameters first. Resolve THD,NTC,FAN orTEC alarms before restarting.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG cabinet environment systems — English product-family brochure.

This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.