ENGINEERED FOR INDUSTRIAL ENVIRONMENTS中文官网 ↗
ENMG
K708T Power relay modules with test-lever options

ENMG / RELAY INTERFACE MODULES

K708T

Power relay modules with test-lever options

DIN interfaces using plug-in K708 power relays, with selectable manual test levers, screw or spring terminals and output protection.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / K708T

Specifications & selection.

Official model patterns
Relay configurationScrewSpringMIL / screwMIL / spring
DPDT basicK708T-**2SK708T-**2MK708T-**2CK708T-**2CM
DPDT test leverK708T-**2TSK708T-**2TMK708T-**2TCK708T-**2TCM
SPDT basicK708T-**1SK708T-**1MK708T-**1CK708T-**1CM
SPDT varistorK708T-**1S-VK708T-**1M-VK708T-**1C-VK708T-**1CM-V
SPDT fusedK708T-**1S-FK708T-**1M-FK708T-**1C-FK708T-**1CM-F
SPDT test leverK708T-**1TSK708T-**1TMK708T-**1TCK708T-**1TCM
SPDT test + varistorK708T-**1TS-VK708T-**1TM-VK708T-**1TC-VK708T-**1TCM-V
SPDT test + fuseK708T-**1TS-FK708T-**1TM-FK708T-**1TC-FK708T-**1TCM-F
Relay technical-image specifications
ParameterSPDT / 1PDPDT / 2P
Resistive load12 A, 250 VAC / 30 VDC8 A, 250 VAC / 30 VDC
Motor load1/3 HP at 240 VAC1/6 HP at 240 VAC
Maximum resistive power3000 VA / 360 W2000 VA / 240 W
Operate / release time≤20 / ≤10 msSame
Electrical / mechanical life100,000 / 10 million operationsSame
Single relay massApproximately 20 gApproximately 20 g
Coil and installation reference
ItemPublished information
Coil options6 / 12 / 24 / 48 / 110 VDC; 24 / 110 / 220 VAC
Coil consumptionDC approximately 0.53 W / AC 1.0 VA
Operate / release thresholdDC ≤75% / ≥10%; AC ≤80% / ≥30% rated
Contact resistanceInitially ≤50 mΩ
Relay withstand: contacts / poles / coil-contact1000 / 3000 / 5000 VAC, 50/60 Hz, 1 minute
Insulation resistance≥1000 MΩ at 500 VDC
Ambient−40 to +55 °C; 5–85% RH; 86–106 kPa
Screw torque / strip0.4 N·m / 6–7 mm in prose
Optional fuse reference6 A / 250 V in prose; confirm actual build
Assembly outline / mass / terminal wire rangeExact K708T drawing and specification required

Selection & installation notes

  • ** is the ordered channel count; the test-lever T is an additional option, not guaranteed merely by the K708T family name. Confirm the full voltage and feature code.
  • Relay ratings are not complete-module ratings. Fused options may be limited by the 6 A fuse, terminal and PCB capacity; verify shared-COM and thermal limits.
  • The source bases its module dimensions on another equivalent interface base, so those dimensions are not presented here as verified K708T production dimensions.
  • The technical image labels an 11 ms half-sine shock pulse as both shock and vibration. A valid vibration specification remains to be confirmed.
  • LED color is described both by AC/DC coil type and NPN/PNP input polarity. Confirm the exact relay and module indicators from markings. Manual testing can energize connected loads without PLC command; restore the test lever before normal operation.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG relays — English product-family brochure.

This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.