m-SDR Integrated-heat-sink solid-state relays

ENMG / SOLID-STATE RELAYS

m-SDR

Integrated-heat-sink solid-state relays

DIN-rail or surface-mounted solid-state relays with a narrow aluminum heat sink, providing SCR AC and optional MOSFET DC output configurations.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / m-SDR

Specifications & selection.

Current prose selection
ModelOutput rangeTriggerControl
m-SDR25A303225 A,48–480 VACZero-cross5–24 VDC
m-SDR40A303240 A,48–480 VACZero-cross5–24 VDC
m-SDR40A313240 A,48–480 VACRandom5–24 VDC
m-SDR40A30L440 A,48–480 VACZero-cross4–20 mA
m-SDR40A31L440 A,48–480 VACRandom4–20 mA
m-SDR25A2032 /40A203225 /40 A,24–280 VAC,customZero-cross5–24 VDC
m-SDR25D6132 /40D613225 /40 A,0–60 VDC,customMOSFET5–24 VDC
m-SDR40D61L440 A,0–60 VDC,customMOSFET4–20 mA
Source thermal and electrical reference
Parameter25 A40 A
Junction/case thermal resistance≤0.35 °C/W≤0.2 °C/W
I²t at10ms in original table1600 A²s3250 A²s
On-state drop in prose≤1.5 V at nominal current≤1.5 V at nominal current
Off-state leakage in prose<10 mA<10 mA
Switching delay in prose≤half cycle+1 ms≤half cycle+1 ms
Installation and inputs
ParameterValue
Voltage control code325–24 VDC;≤10 mA in prose; off<1 V
Current control L44–20 mA; transfer function and burden not specified
DC variants0–60 VDC reference;Ron not supplied; require order datasheet
Ambient−30 to +80 °C;≤90% RH, non-condensing; derating required
Mounting35 mm DIN rail or surface screws
Original outline104 ×23 ×101.5 mm;94 mm mounting-center spacing
Prose outline /mass104 ×22.5 ×101 mm /approximately350 g
TerminalsM3 input /M4 output; obtain terminal-specific torque
Important source discrepancies
ItemDetails
AC voltage chartOriginal chart is25A2032/40A2032,24–280 VAC; current prose emphasizes3032,48–480 VAC
25 A blocking voltageProse says≥600 V peak; original2032 table1600 V.600 V alone does not establish480 VAC capability
Surge rowOriginal image has voltage units in a surge-current row; prose gives180/850 A at10ms. Obtain corrected ratings
L4 behaviorProse says on at≥4 mA but does not define proportional transfer, burst or phase-angle behavior

Selection & installation notes

  • Do not combine specifications from the2032 chart with a3032 ordered variant. Confirm blocking voltage, surge waveform and correctedI²t data before fuse selection, especially for480 VAC service.
  • A random-trigger relay needs a suitable synchronized controller for phase-angle control; a generic DC input alone is not an analog voltage regulator. Confirm what the L4 variant actually implements.
  • The heat sink does not eliminate derating. Obtain the exact curve, airflow and junction-temperature limits; generic80% or10%-per10°C rules are not guaranteed ratings.
  • Protect inductive loads against transients using a load-specific circuit. Verify inrush and the intended application before motor, transformer or capacitor switching.
  • Output-off is not isolation. Provide a suitable upstream disconnect and semiconductor protection; isolate both circuits before service.
  • The naming explanation omits a field that appears in the listed DC codes. Order by a confirmed complete part number, not by combining naming fragments.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG relays — English product-family brochure.

This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.