ENGINEERED FOR INDUSTRIAL ENVIRONMENTS中文官网 ↗
ENMG
RT-M04E-K2 / K3 Four-channel relay modules for solenoid and hydraulic valves

ENMG / RELAY INTERFACE MODULES

RT-M04E-K2 / K3

Four-channel relay modules for solenoid and hydraulic valves

G2R-1-E relay interfaces with load-specific suppression: shared-common DC outputs in K2 and independent AC outputs in K3.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / RT-M04E-K2 / K3

Specifications & selection.

Selection
ModelOutputSuppression
RT-M04E-K2Four normally open; shared COM; DCRC across contacts and diode across load
RT-M04E-K3Four independent normally open; AC10D471K varistor across each output
Relay-level reference
ParameterSpecification
RelayG2R-1-E; SPDT
Contact class16 A at 250 VAC / 30 VDC; not assembly rating
Initial resistance≤50 mΩ
Mechanical / electrical lifeOver 20 million / 100,000 operations; test loads not given
Operate / release≤15 / ≤10 ms
Coil options24 VDC; 12 and 5 VDC listed as alternatives
Assembly data
ParameterSpecification
Outline61 × 88 × 55 mm
TerminalsM2.5; 5.0 mm pitch; 10 A / 300 V
Wire / torque / strip22–12 AWG / 0.4 N·m / 6–7 mm
Withstand2500 VAC, 1 minute; test points not specified
Ambient−40 to +70 °C; 5–85% RH; no condensation or icing
Protection designationIP20
K2 RC in circuit drawing100 Ω + 103K / 630 V capacitor; confirm production components

Selection & installation notes

  • Terminals are rated 10 A, below the 16 A relay class. Confirm per-channel and shared-COM limits and thermal derating before load selection.
  • The circuit drawings show 1N4007 coil diodes and a polarized input circuit, while generic prose describes bidirectional TVS and non-polarized indication. Follow the exact supplied diagram; input polarity is not assumed interchangeable.
  • K2 and K3 suppress different loads. Confirm maximum load voltage and suppression energy; built-in components are not universal protection for every solenoid.
  • Isolate both control and load supplies before service. The module exposes normally open outputs; the relay SPDT designation does not establish an accessible NC output.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG relays — English product-family brochure.