TECHNICAL DATA / RT-P04S-K / RT-E04S-K

Specifications & selection.

Electromagnetic selection
ModelSupplyPublished input currentOutline
RT-P04S-K 24V24 VDC7 mA67 × 33 × 38 mm
RT-P04S-K 12V12 VDC11 mA67 × 33 × 38 mm
RT-P04S-K 5V5 VDC23 mA67 × 33 × 38 mm
RT-E04S-K 24V24 VDC7 mA67 × 33 × 38 mm
RT-E04S-K 12V12 VDC11 mA67 × 33 × 38 mm
RT-E04S-K 5V5 VDC23 mA67 × 33 × 38 mm
Solid-state alternatives
ModelInput per channelLoad row in sourceOutline
RT-EQZ102D-04S-K24 VDC / 10 mA3.6 A / 60 VDC67 × 33 × 37.5 mm
RT-EQZ202D-04S-K24 VDC / 10 mA2.7 A / 60 VDC or AC; confirm waveform rating67 × 33 × 37.5 mm
RT-EQG22024-04S-K24 VDC / 10 mA2 A / 75–264 VAC67 × 33 × 37.5 mm
Electromagnetic relay reference
ParameterValue
Contact form / rated loadSPST-NO / 5 A at 250 VAC or 30 VDC
Initial contact resistanceMaximum 30 mΩ
Mechanical / electrical lifeOver 20 million / 100,000 operations; load conditions not supplied
Coil power110 mW per channel; excludes module circuit consumption
Operate / release10 / 5 ms
Coil thresholdsOperate 70%, release 5% of rated voltage
Assembly installation
ItemValue
Terminal torque0.3–0.5 N·m on exact product page
Protection / indicationFlyback and transient suppression; LED
Ambient−20 to +55 °C; 35–85% RH; no condensation or icing
Mass / dimensional toleranceApproximately 100 g / ±0.5 mm

Selection & installation notes

  • P uses PA-N; E uses APAN. The official photograph shows APAN relays and illustrates the E alternative. Confirm the actual fitted relay.
  • The input-current table does not explicitly state whether its electromagnetic figures are per channel. Confirm PLC output loading; do not calculate it solely from 110 mW coil power.
  • Confirm jumper polarity and bridge-bar total-current capacity before commoning. Isolate power before wiring or replacing relays.
  • Derate contact loads for inductive or inrush service. SSR alternatives have leakage and ON-state losses; confirm exact AC/DC applicability, especially EQZ202D.
  • This page specifies torque and ambient limits different from generic family manuals; confirm the supplied product instructions.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.