ENMG / RELAY INTERFACE MODULES
RT-P32S-L
32-channel fused relay terminal module
A 32-channel PA-N relay interface with screw-terminal outputs, four outputs per common group and replaceable output fuses.
Request a quote ↗TECHNICAL DATA / RT-P32S-L
Specifications & selection.
- NPN/PNP compatible input; default 24 VDC, 5/12 VDC versions.
- Plug-in miniature relays with SPST-NO outputs.
- 35 mm DIN installation and per-channel status indicators.
| Parameter | Specification |
|---|---|
| Outputs / grouping | 32 / four per COM |
| Output terminals | Screw; S code |
| Output fuse | 5 A / 250 V slow-blow per channel |
| Relay load class | 5 A at 250 VAC / 30 VDC; resistive |
| Outline L × W × H | 220 × 87 × 50 mm |
| Mass | Not specified |
| Parameter | Published value |
|---|---|
| Relay / contact | PA-N / 1a, source describes double contact |
| Initial resistance | ≤30 mΩ |
| Mechanical / electrical life | Over 20 million / 100,000 operations; test load not supplied |
| Coil / consumption | 5 / 12 / 24 VDC; 110 mW per channel, coil only |
| Operate / release threshold | ≤70% / ≥5% rated voltage |
| Operate / release time | 10 / 5 ms |
| Input protection | miniSMDC050F 500 mA resettable fuse; SMF36CA 36 V bidirectional TVS |
| Indicator | Red/green non-polarized LED |
| Parameter | Published value |
|---|---|
| Screw terminals | M2.5; 5 mm pitch; 10 A / 300 V |
| Wire / strip / torque | 22–12 AWG / 6–7 mm / 0.4 N·m |
| Withstand | 2500 VAC, 1 minute; test points not given |
| Ambient | −40 to +70 °C; 5–85% RH; no condensation or icing |
| Ingress / flammability designation | IP20 / UL94 V-0 in source |
Selection & installation notes
- Four 5 A channels sharing COM do not establish 20 A group capacity. The terminal is rated 10 A; obtain the lower applicable complete-module and shared-COM limit with thermal derating.
- The 72 mm base designation differs from the 87 mm overall width. Use the full 220 × 87 × 50 mm drawing for layout and confirm the production version.
- Match the fuse time-current characteristic and AC/DC breaking capacity to the actual load circuit; a 250 V marking alone does not establish DC interruption capability.
- The E-series APAN variant is a separate order code; do not substitute coil or suppression ratings without confirmation. De-energize before replacing a relay or fuse.
Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.
TECHNICAL RESOURCES
Plan your integration.
ENMG relays — English product-family brochure.
This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.