TECHNICAL DATA / RT-SSK-M

Specifications & selection.

Relay selections and fitted fuse limits
RelaySemiconductor output classPublished fitted fuse
SSK4A20324 A, 75–264 VAC, 45–65 Hz TRIACØ5 × 20 mm aR RS54 2 A / 250 V
SSK4D61324 A, 5–60 VDC transistorØ5 × 20 mm aR RS54 2 A / 250 V
SSK10D613210 A, 0–60 VDC MOSFETImage: 2 A; prose: 5 A — confirm supplied fuse
SSK4K61324 A, 24 VAC/DCØ5 × 20 mm aR RS54 2 A / 250 V
Model construction
PositionCode
Model formatRT-[relay model]-[channels][terminal]-F
Channels02 / 04 / 06 / 08 / 10 / 12 / 16
TerminalsM: spring; S: screw; 16CM / 16C: MIL-input versions
ExampleRT-SSK10D6132-08M-F
Protection-F: output fuse; unmarked versions do not imply fitted protection
Electrical characteristics
Parameter4A AC4D DC10D DC
On-state drop≤1.2 V at 2 A≤1.3 V at 2 A≤0.3 V at 10 A
Off-state leakage≤3 mA at 240 VAC≤1 mA at 60 VDC≤1 mA at 60 VDC
Switching time≤half cycle + 1 ms≤1 ms≤1 ms
Nonrepetitive surge, duration unspecified30 A16 A180 A
Module and installation data
ParameterValue
Input5–24 VDC nominal; 3–32 VDC stated range; one COM polarity per module
Input indicationCOM+: green; COM−: red
Withstand / insulation2500 VAC, 50/60 Hz, 1 minute / ≥1000 MΩ at 500 VDC
Ambient−30 to +80 °C; 45–85% RH, no condensation or icing
Screw terminalsM2.5, pitch 5 mm; 22–12 AWG; 0.4 N·m; strip 6–7 mm
Spring terminalsPitch 5 mm; 22–16 AWG, 1.5 mm² maximum; strip 8–9 mm
Width by 2/4/6/8/10/12/16 channels40 / 70 / 100 / 130 / 160 / 200 / 260 mm
Other outline dimensions83 × 50 mm; approximate, verify full assembly drawing
Mounting35 mm DIN rail

Selection & installation notes

  • The relay semiconductor current is not the permissible continuous current of the complete fused module. The standard 2 A fuse constrains the 4 A relay options; the 10 A option has conflicting 2 A/5 A fuse specifications. Confirm the actual fuse, thermal derating and total simultaneous load before ordering.
  • Use the approved semiconductor fuse with suitable voltage, interrupt rating and I²t coordination. Do not uprate a supplied fuse to obtain the relay headline current.
  • Derate above 40 °C and allow ventilation. Surge values without pulse duration are not repetitive-load ratings.
  • NPN/PNP flexibility applies to the input common only. Verify output polarity, suppression and the wiring of any custom common connections.
  • Off-state leakage is not electrical isolation. Isolate power before wiring, relay replacement or MIL connection changes.