ENMG / SOLID-STATE RELAYS
SSK DIN-rail socket sets
SSK solid-state relays with DIN-rail sockets
SSK semiconductor relay and compatible G2R/G2RL-format socket combinations for 35 mm DIN-rail installation.
Request a quote ↗TECHNICAL DATA / SSK DIN-rail socket sets
Specifications & selection.
- Non-polarized control input.
- 5-pin and 8-pin footprint families.
- TRIAC AC outputs and low-resistance DC options.
| Input | Basic DC | Low-resistance DC | Non-polarized | AC zero-cross | AC random |
|---|---|---|---|---|---|
| 5–24 VDC, code 32 | SSK3D6132 / SSK4D6132 | SSK10D6132 | SSK4K6132 | SSK3A2032 / SSK4A2032 | SSK4A2132 |
| 24 VDC, code 24 | SSK4D6124 | SSK10D6124 | Not listed | SSK4A2024 | SSK4A2124 |
| Suffix | Nominal | Operating range | Approximate impedance |
|---|---|---|---|
| 05 | 5 VDC | 4–6 VDC | 0.5 kΩ |
| 12 | 12 VDC | 9.2–14.4 VDC | 1.5 kΩ |
| 24 | 24 VDC | 19.2–28.8 VDC | 2.2 kΩ; 3.3 kΩ in 4K group |
| 32 | 5–24 VDC | 3–32 VDC | Not stated |
| Parameter | 3A / 4A | 3D / 4D | 10D | 4K |
|---|---|---|---|---|
| Current | 3 / 4 A | 3 / 4 A | 10 A | 4 A |
| Voltage | 75–264 VAC, 45–65 Hz | 5–60 VDC | 0–60 VDC | 0–60 V AC/DC text; AC peak limit applies |
| Non-repetitive surge; duration unspecified | 30 A | 16 A | 180 A | 180 A |
| Peak withstand | 600 V | 60 V | 60 V | 60 V |
| ON voltage | ≤1.2 V at 2 A | ≤1.3 V at 2 A | ≤0.6 V at 10 A | ≤1.2 V at 4 A |
| OFF leakage | ≤3 mA at 240 VAC | ≤1 mA at 60 VDC | ≤1 mA at 60 VDC | ≤0.01 mA at 60 VDC |
| Minimum load | 20 mA | 20 mA | 20 mA | 0.02 mA in source; confirm unit |
| Switching time | ≤half cycle + 1 ms; random turn-on ≤1 ms | ≤1 ms | ≤1 ms | ≤1 ms |
| Parameter | Published specification |
|---|---|
| Input current | Approximately 10 mA, range 5–15 mA |
| Dielectric / insulation | 2500 VAC, 50/60 Hz, 1 minute / ≥1000 MΩ at 500 VDC, input–output |
| Vibration / shock | 10–55 Hz, 0.75 mm double amplitude / 1000 m/s² |
| Operation / storage | −30 to +80 °C / −30 to +100 °C |
| Humidity | 45–85% RH; no condensation or icing |
| Maximum body outline / mass | 29 × 12.7 × 16 mm, excluding pins / approximately 20 g |
| Socket options, 5-pin / 8-pin | RSZE05P / RSZE08P; RS-ZE2M-35M / -48M; G2R-1-SSG / -2-SSG |
Selection & installation notes
- SSK4K AC voltage must stay within the stated 60 V peak limit; 60 VAC RMS must not be inferred. Confirm the exact AC rating and minimum-load unit.
- Footprint similarity does not make a semiconductor output equivalent to changeover mechanical contacts. Verify pinout, output polarity, leakage and the selected socket rating.
- The photograph illustrates an SSK10D6132 relay on an RS-ZE2M-48M cage-terminal socket. Relay-only dimensions and ratings do not establish the complete set outline or combined rating.
- Choose suppression and fast protection for the actual load. Derate above 40 °C and for dense mounting; surge figures lack duration. Isolate power before service.
- Source PCB soldering limit: below 260 °C, within 10 seconds. Request the production footprint before board design.
- Confirm the complete relay/socket combination, retaining clip, wire range, strip length and terminal torque. Do not use relay PCB body dimensions for DIN cabinet spacing.
Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.
TECHNICAL RESOURCES
Plan your integration.
ENMG relays — English product-family brochure.