ENGINEERED FOR INDUSTRIAL ENVIRONMENTS中文官网 ↗
ENMG
GM / GL / SM / SL Plug-in solid-state relays for MY and LY socket formats

ENMG / SOLID-STATE RELAYS

GM / GL / SM / SL

Plug-in solid-state relays for MY and LY socket formats

Socket-format semiconductor relays with AC or DC output options, offered in aluminum or plastic housings and narrow or wide pin styles.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / GM / GL / SM / SL

Specifications & selection.

Official model chart
Housing / pinsOutput formDC outputAC zero-crossAC random
GM / narrow1 NOGM5D6132GM5A2032GM5A2132
GM / narrow2 NOGM2D6132-20GM2A2032-20Not listed
GM / narrow1 NO + 1 NCGM2D6132-11Not listedGM2A2132-11
SM / narrow1 NOSM5D6132SM5A2032SM5A2132
SM / narrow2 NOSM2D6132-20SM2A2032-20Not listed
SM / narrow1 NO + 1 NCSM2D6132-11Not listedSM2A2132-11
GL / wide1 NOGL15D6132Not listedNot listed
GL / wide2 NOGL5D6132-20Not listedNot listed
SL / wide1 NOSL15D6132Not listedNot listed
SL / wide2 NOSL5D6132-20Not listedNot listed
Output and control reference
ParameterValue
AC label GM5A203224–240 VAC, 5 A, zero-cross
DC GM5D61325–60 VDC, 5 A
DC GL15D613215 A; source selection says 5–60 VDC, body marking says 0–60 VDC
Input code 32 / 245–24 VDC / 12–24 VDC; confirm ordered variant
Current codes2A / 5A: 2 / 5 A AC; 2D / 5D / 15D: 2 / 5 / 15 A DC
Timing, leakage, surge and derating curvesNot specified in source
Dimensions / massExact model and socket drawing required

Selection & installation notes

  • MY/LY form-factor similarity does not establish electrical drop-in compatibility. Verify every input/output pin, polarity, NO/NC behavior, minimum load and socket rating before replacement.
  • The source socket table mixes connection-style labels. Match the physical pin format and manufacturer drawing; do not select solely from its spring/cage/barrier headings.
  • Use AC-output models only on suitable AC loads and DC-output models only on suitable DC loads. The 0–60 versus 5–60 V GL15D marking requires confirmation.
  • Semiconductor outputs leak when off and do not provide safe isolation. Confirm load compatibility and provide external isolation for service.
  • Current depends on cooling, socket limits, inrush and simultaneous outputs. Aluminum housing alone does not guarantee full rated current in an enclosed cabinet; request thermal and protection data.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG relays — English product-family brochure.

This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.