ENGINEERED FOR INDUSTRIAL ENVIRONMENTS中文官网 ↗
ENMG
ST5 / ST8 Five- and eight-channel solid-state driver modules

ENMG / SOLID-STATE DRIVER MODULES

ST5 / ST8

Five- and eight-channel solid-state driver modules

Compact multi-channel interfaces with non-isolated Darlington, optically isolated DC and optically isolated AC output families.

Request a quote ↗

View specifications ↓

TECHNICAL DATA / ST5 / ST8

Specifications & selection.

DC model selection
ModelIsolationPolarityLoad voltage
ST5P-5D-NNon-isolatedCOM+ input / COM− output24 VDC ±20%
ST5N-5D-PNon-isolatedCOM− input / COM+ output24 VDC ±20%
ST5P-5DDOptical DCDual-polarity input / COM− output5–60 VDC
ST5N-5DDOptical DCDual-polarity input / COM+ output5–60 VDC
ST8P-5D-NNon-isolatedCOM+ input / COM− output24 VDC ±20%
ST8N-5D-PNon-isolatedCOM− input / COM+ output24 VDC ±20%
ST8P-5DDOptical DCDual-polarity input / COM− output5–60 VDC
ST8N-5DDOptical DCDual-polarity input / COM+ output5–60 VDC
AC model selection — 24–280 VAC, 50/60 Hz
ModelInputMOVTrigger
ST5-5DA-NCOM+NoZero-cross; random option requires confirmed order code
ST5-5DADualNoZero-cross; random option requires confirmed order code
ST5-5DA-VDual10D511KZero-cross; random option requires confirmed order code
ST5-5DA-NVCOM+10D511KZero-cross; random option requires confirmed order code
ST8-5DA-NCOM+NoZero-cross; random option requires confirmed order code
ST8-5DADualNoZero-cross; random option requires confirmed order code
ST8-5DA-VDual10D511KZero-cross; random option requires confirmed order code
ST8-5DA-NVCOM+10D511KZero-cross; random option requires confirmed order code
Output technical comparison
ParameterNon-isolated DCOptical DCOptical AC
Continuous / total current5 A / ≤10 A5 A / ≤10 A5 A / ≤10 A
Peak withstand60 V60 V800 V
Short-time / non-repetitive surge10 / 20 A10 / 20 A16 / 180 A
ON drop1.2 V1.2 V1.5 V
OFF leakage≤1 mA≤1 mA≤3 mA
ON / OFF≤1 / ≤1 ms≤1 / ≤1 ms10 / 1 ms at 50 Hz in source; confirm turn-off condition
ProtectionFlyback diodeExternal flyback required for inductive loadRC; MOV on V variant
Isolation withstandNone3750 V; duration not stated3750 V; duration not stated
Installation
ItemSpecification
ST5 outline / terminals51 × 65 × 30 mm / 12
ST8 outline / terminals75 × 65 × 30 mm / 18
TerminalsBarrier M3; 8 mm pitch; wire ≤1.25 mm²; 1.2 N·m
Ambient−40 to +70 °C; 5–85% RH; no condensation or icing
Reference temperature25 °C
Non-isolated control voltageConfirm before selection; not given

Selection & installation notes

  • All channels share a 10 A total limit. Derate and provide forced cooling at or above 40 °C as specified by the source; obtain the actual curve.
  • Surge and short-time current durations are missing. Do not use these figures as continuous ratings. The AC turn-off row needs waveform-specific confirmation.
  • The page states MOV changed to 10D511K on 2026-08-20; confirm the supplied revision. The 800 V Triac peak value is not an operating load voltage.
  • For AC loads below 75 V, the source advises checking zero-cross compatibility or using a suitable random-trigger variant. Confirm leakage and minimum-load compatibility.
  • Use properly coordinated semiconductor protection. OFF-state leakage is not electrical isolation; disconnect main power before servicing.

Based on the official Chinese product page and selection charts ↗. Checked 2026-09-15. Confirm the current specification for the exact model when ordering.

TECHNICAL RESOURCES

Plan your integration.

ENMG relays — English product-family brochure.

This is a product-family brochure. Request a model-specific datasheet and installation drawing with your inquiry.